7.) The lack of "in use" type covers on outdoor receptacles.

Section 406.8(B) Wet Locations.

(1) 15- and 20-Ampere Outdoor Receptacles. 15- and 20-ampere, 125- and 250-volt receptacles Installed outdoors in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted.
(2) Other Receptacles. All other receptacles installed in a wet location shall comply with (a) or (b):
(a) A receptacle installed in a wet location where the product intended to be plugged into it is not attended while in use (e.g., sprinkler system controller, landscape lighting, holiday lights, and so forth) shall have an enclosure that is weatherproof with the attachment plug cap inserted or removed.
(b) A receptacle installed in a wet location where the product intended to be plugged into it will be attended while in use (e.g., portable tools and so forth) shall have an enclosure that is weatherproof when the attachment plug is removed.

| 2002 Installation Deficiencies |